YAKY 0,6/1kV – PVC Insulated Cable with Aluminium Conductor

Application:
This power cable is suitable for fixed installations, preferably in cable ducts, indoors, outdoors, in water or underground if no mechanical damage is to be expected
Construction:
Conductor - Solid (RE/SE) or Stranded (RM/SM) aluminium wires
Insulation - Core insulation of Polyvinylchloride (PVC)
Filling - PVC core covering or taping
Outher sheath - Polyvinylchloride (PVC), Black
Standards:
IEC 60502
HD 308 S2
IEC 60228
License:
VDE
Electrical Performance:
Nominal Voltage: 600/1000 Volt
Test Voltage: [V]AC 4000
Short circuit time max. [sec] 5
Bending radius:  single core x diameter 15
Bending radius: multi core 12
Temperature range:
In motion °C -5°C till +70°C
Fixed °C -30°C till +70°C
Maximum short circuit temperature:  160°C <=300mm2  
Maximum short circuit temperature: 140°C > 300mm2
Fire classification CPR class:
EN 50575 - Eca